Fixing Duct Leaks In Commercial Buildings

aeroseal_logo_500

In contrast to residences, standards dealing with duct leakage in commercial buildings have existed for many years (e.g., SMACNA’s HVAC Air Duct Leakage Test Manual [1985]). However, duct leakage is common in certain types of commercial buildings, and in certain system components. Unfortunately, these problems have had little attention.

Examples of this inattention to duct leakage include typical light commercial strip malls. They also include large existing commercial buildings that did not receive adequate duct tightness testing either during construction or when construction, performance, or operation changed significantly. Another issue is inattentiveness to commercial building duct system components downstream of VAV boxes.

This article discusses issues associated with duct leakage in these types of buildings and components, and presents case studies of leakage measurements and repair in these applications. 

Building Classification

The question of when duct leakage is significant in a commercial building depends heavily upon the building type and duct system, the location of leakage, and the amount of leakage. Key distinguishing factors between commercial buildings are whether they are similar in size and equipment type to residences, or whether they contain larger, more complex HVAC systems. The first group of buildings is referred to in this article as thermally dominated commercial buildings. The second group is large commercial buildings whose HVAC energy use is more heavily impacted by fans.

Thermally Dominated Commercial Buildings

A thermally dominated commercial building works much like a single-family sunbelt residence, typically conditioned by duct work located above the ceiling, and connected to small rooftop packaged equipment with fans that often cycle with the call for heating or cooling. In these buildings, the majority of the HVAC energy consumption is for heating and/or cooling the air, rather than the fan.

Large Commercial Buildings

In large commercial buildings, the operation of the fan(s) usually is not in direct synchronization with heating and cooling delivery. The fans typically run constantly, although often not at a constant flow rate, during building operation. In addition, the longer transport distances and control requirements in large buildings also translate into higher pressure differentials experienced by the central fan(s). The combination of these factors translates into a higher fraction of HVAC energy consumed by the fan, even though many of the fans have higher efficiencies than those found in standard packaged HVAC equipment.

Impacts of Duct Leakage

Ducts in the ceiling plenum space may appear to be in the conditioned space but are not. Fan power can be impacted by duct losses even if all the thermal energy returns to the conditioned spaces. As is discussed later, a ceiling plenum space has different energy implications depending on where the insulation is located, and whether the ceiling plenum is used as a return or exhaust duct. In a light commercial strip mall (thermally dominated commercial building), the key determinants of duct leakage energy implications are the degree of leakage, and the location of the ductwork relative to the thermal and air boundaries of the conditioned space. At one end of the spectrum is ductwork that can be seen from within the occupied space, for which there is little energy to be saved by sealing or insulating that ductwork.

On the other hand, when ductwork is located above a “T-bar” or plaster ceiling, the thermal resistance of the ceiling relative to the roof is a key determinant of how much energy savings can be realized. The relative tightness of the ceiling with respect to the roof deck also is significant.

Field studies in California have shown that the insulation in light commercial buildings can be found on the ceiling, on the roof, or in both places (Figure 1), and that a non-trivial fraction of the buildings tested (38%) had ceiling tiles acting as the air barrier of the building due to the installation of turbine vents on the roof that make the roof less airtight than the ceiling.

Another study indicated that California buildings that received building permits during a time that required roof insulation showed a much smaller fraction of ceiling insulation (2). Interestingly, a limited study in Wisconsin did not have any trouble finding buildings with ceiling insulation (3).

To quantify the significance of the location of building insulation and air barriers, ANSI/ASHRAE Standard 152-2004, Method of Test for Determining the Design and Seasonal Efficiencies of Residential Thermal Distribution Systems, was applied to the three types of ceiling plenum configurations for Bakersfield, Calif., Milwaukee and Atlanta.*

*Although Standard 152-2004 was designed for residential systems, the results it provides for light commercial retail or office buildings are not exact, but are workable. Factors that reduce the appropriateness of these results include large exhaust fans for cooking, or operating conditions that vary dramatically from those for residences.

All of the Standard 152-2004 analyses are based upon the assumption that the fan is cycling with the equipment. The additional energy implications of continuous fan operation, although not incorporated into Standard 152-2004, have been shown to depend upon the duty cycle of the heating/cooling equipment.4 Continuous fan operation has the largest negative impacts at low part load ratios.

Standard 152-2004 underestimates the influence of insulation location for a light commercial ceiling plenum, as the temperatures in the plenum are not calculated, and the impact of the insulation only is captured via the fraction of duct losses recovered. Efficiencies should be higher, and percentage savings should be somewhat lower for roof-only configurations. However, as most losses are regained (90% regain) in roof-only insulation configurations, these effects should be relatively modest.

Duct Leakage in a Large Commercial Building

In large commercial buildings, several mechanisms exist by which energy use is impacted by duct leakage and conduction losses. One mechanism is the effective short circuiting of heating and cooling energy back to the return prior to reaching the desired zone. This short circuiting means that the fan has to move more air to meet a given load, thereby increasing the fan energy non-linearly (5).

At the most basic level, fan power increases with fan flow raised a power between 2 and 3, stemming from the fact that fan power scales with the product of fan pressure differential and flow, and that the pressure differential increases with the flow raised to a power between 1 and 2. Using the power 2.4 from Franconietal.,5 a 15% leak translates to a 40% increase in fan power.

A secondary impact of the increased fan power is an increase in cooling load associated with the heat generated by the increased fan power, resulting in higher cooling energy use.

Another mechanism by which duct losses in large commercial buildings increase energy use stems from the fact that thermal losses to the return air are not all recaptured by the building or the HVAC system. Some fraction of return air typically is exhausted from the building, thereby throwing away that fraction of the supply air thermal energy lost to the return airstream. This fraction of air exhausted can be as high as 100% in buildings such as laboratories, hospitals or casinos.

Other factors that determine the energy impacts of duct leakage or conduction losses include the use of ceiling plenum returns and the use of induction VAV boxes. The use of ceiling plenum returns vs. ducted returns tends to increase the energy impacts of supply duct leakage, as all of the losses to a ceiling plenum return go directly to the return/exhaust, whereas a larger fraction of the supply losses are likely to be drawn into the conditioned spaces before being pulled into ducted returns.

The degree to which supply losses make it to the conditioned space in ducted return systems depends upon the pressure in the ceiling plenum relative to the conditioned space, which in turn depends somewhat upon the ratio of supply to return duct leakage.

In the case of ceiling plenum returns, most of the energy lost to the ceiling plenum tends to be returned or exhausted due to the larger effective UA value (thermal conductance) of the return/exhaust airstream as compared to the UA value of the ceiling. In this type of construction, fan powered or system powered induction boxes tend to reduce the energy impacts of supply duct leakage, as the airflows drawn from the ceiling plenum reduce the fraction of the supply losses that are returned to the system fan. The induction flows can be thought of as a form of recovery of supply duct losses.

To place these energy flows in perspective, consider that a return airflow of 0.85 cfm/ft2 (4.3 L/s/m2) has an effective thermal conductance of 0.92 Btu/h/°F per ft2 of floor area (5.2 W/°C/m2). Assuming that the ceiling area is equal to the floor area, this conductance should be compared to a ceiling thermal conductance of 0.32 Btu/h/°F (1.8 W/°C), corresponding to a 0.75 in. (1.8 cm) thick acoustical ceiling tile. On the other hand, induction box flows can be less than, equal to, or greater than system fan flows, depending on the load of the space.

Supply losses to ceiling plenums also affect economizer and terminal reheat coil operation. For economizers, the colder return air temperature associated with supply air cooling losses to the return air decrease the use of economizers controlled by return air temperature, decreasing the temperature at which outside air is introduced. For terminal reheat coils, assuming that the minimum settings at the VAV boxes are not adjusted, supply duct leakage reduces minimum airflows at the coils, thereby reducing reheat coil energy use during minimum air operation.

One final consideration with respect to ceiling plenums is that thermal recovery of supply losses by conditioned spaces does not necessarily improve matters during simultaneous heating and cooling, where cooling losses can be recovered by zones that require heating, and vice versa.

Although all of these effects have not been quantified on a systematic basis, Franconietal.,5 uses detailed building and system simulation to provide a reasonable quantification of the impacts of duct leakage in a large commercial building, calculating a 60% increase in fan power due to 20% duct leakage split on average equally between upstream and downstream of the VAV boxes. Those simulation results also show little impact of part load ratio on the percentage savings. Diamond et al.,6 measured an increase in system fan power of 25% to 35% due to increasing duct leakage from 5% to 20%.

Uncontrolled Airflows

Another impact of duct leakage in commercial buildings that is not discussed in this article is that of leakage on uncontrolled airflows and pressures.7 The impacts of these uncontrolled air flows often are much larger than the energy implications of that leakage, ranging from depressurization causing moisture damage in walls and back drafting of combustion equipment, to transport and disperse of chemical or biological pollutants.

Field Measurements of Duct Leakage

Published measurements of duct leakage in light commercial buildings have generally been limited to Florida and California. Delp et al., summarizes duct leakage results from Florida and California, expressing the leakage in terms of effective leakage area (effective hole size) per unit floor area. The reported values were 0.053 in.2/ft2 floor area (3.7 cm2/m2 floor area) for 25 California light commercial systems, 0.039 in.2/ft2 floor area (2.7 cm2/m2 floor area) for 39 Florida light commercial systems, and 0.019 in.2/ft2 floor area (1.3 cm2/m2 floor area) for California residential systems. Although the size of the holes in the ducts is a convenient tool for comparing construction quality, it has to be combined with the pressures across the leaks to determine their impact on energy performance. Delp et al., also presents a comparison of measured fan flows and supply grille flows for 35,000 ft2 (3250 m2) of light commercial floor space in California, which indicated 1.24 cfm/ft2 (6.3 L/s/m2) at the fan, and 0.92 cfm/ft2 (4.7 L/s/m2) at the grilles, or supply duct leakage of 26% of fan flow.

A much larger data set of light commercial duct leakage areas was acquired in a pilot test of duct sealing for electric demand reduction in Southern California. The average measured pre sealing leakage for 364 light commercial duct systems tested in this study was 0.03 in.2/ft2 floor area (2 cm2/m2 floor area), calculated based upon assuming 340 ft2 of floor area per ton of air-conditioning capacity (9 m2 per kW cooling capacity).

Existing Large Commercial

Considerably less published scientific data exists on duct leakage in large commercial buildings as compared to light commercial buildings, mostly due to the extra difficulties associated with making leakage measurements in these buildings. One difficulty in large buildings is their size and accessibility, leading to much higher measurement costs. Another difficulty with duct leakage measurements in large commercial buildings is the temporal variability of fan, branch and leakage flow rates.

As it is generally impractical to seal all the diffusers simultaneously and measure leakage flow under a presumably uniform duct pressure in a large commercial building, one way of avoiding the size issue is to measure the leakage of a sample duct system branch. This technique involves isolating the branch at the VAV box, and thus does not provide a measurement of leakage upstream of the VAV boxes. Several techniques for measuring duct leakage upstream of the VAV boxes based upon closing those dampers are the subject of current research, as is a technique that determines branch leakage flow by subtracting the sum of diffuser flows from a branch flow measurement under a representative flow condition.

The duct leakage value needed to evaluate the appropriateness of sealing is the percentage of fan flow being leaked. As noted earlier, this can sometimes be measured directly, but often is based upon separate measurements of duct leakage area and operating pressures. In large buildings, this process is complicated by the variable operating conditions of different parts of the system. Specifically, leaks upstream of the VAV dampers generally see a relatively constant pressure determined by the pressure set point of the system fan. Therefore, the flow through these leaks is relatively constant in absolute terms, but variable as a percentage of fan flow.

On the other hand, the flows through leaks downstream of the VAV dampers vary almost proportionally to the branch flow rate(leaks vary with duct pressure to the power 0.6, whereas branch flow varies with VAV box pressure to the power 0.5). Thus, downstream leaks represent a relatively constant percentage leakage. The variations in pressures seen by leaks that influence the leakage flows are further compounded by spatial variations in leakage levels (e.g., leaks at diffusers vs. at VAV boxes) that make the variations in pressure more important.

Another key issue in large commercial duct leakage is the large variability of the results to date. Researchers at Lawrence Berkeley Laboratory measured duct leakage in six large commercial buildings, three of which showed 5% leakage, while the other three showed 15%, 17% and 25% supply duct leakage.

While duct leakage measurements are limited, test and balance reports that include fan flow as well as diffuser flow measurements could be used under certain circumstances. One limitation of these measurements is that some test and balance protocols are single pass, whereby each diffuser damper is adjusted on the spot to produce the desired flow. A similar problem occurs when VAV boxes are not all opened simultaneously during testing, which is a fairly common protocol. In both cases, the difference between the fan flow and the sum of diffuser flows is no longer a good estimate of duct leakage (generally underestimating leakage).

Duct Sealing in Commercial Buildings

A recent development in sealing duct leakage in commercial buildings involves a technology that seals leaks from the inside out. This technology, known as aerosol-based sealing, works by pressurizing a duct system with a fog of sealant particles. By temporarily blocking the diffusers, the sealant laden air is forced to the leaks. Maintaining mild turbulence keeps the sealant particles suspended until they reach the leaks. The pressure maintained within the duct system causes the air to accelerate as it exits through the leaks, causing the particles to be flung against the walls of the leaks when they cannot turn as sharply as the accelerating air.8,9,10

Due to its ability to access leaks without accessing the exterior of ductwork located above a ceiling, the aerosol-based sealing technology has been used during the last few years to seal duct leaks in light and large existing commercial buildings.

Light Commercial Sealing Results

The systems sealed are located in San Bernadino, Riverside, and Orange counties, and were screened by the HVAC contractors to have ceiling insulation below the ductwork. Of the 360 systems sealed, 300 had complete data acquired, including data on the size of the equipment.

The average equipment size was 3.9 tons (14 kW) and the median size was 3.5 tons (12 kW), with the smallest unit having 2 tons (7 kW) of capacity, and the largest 12.5 tons (44 kW). As indicated in Figure 4, all of the HVAC contractors had approximately the same level of performance, sealing approximately 80% of the leakage encountered, which resulted in duct systems with leakage of approximately 16 cfm/ton of cooling (3.4 cm2 per kW of cooling) after the process.

In addition to showing that the technology could seal a significant majority of duct leakage encountered in these types of existing buildings, this field study also demonstrated that the sealing process could be performed on a production basis, with one contractor regularly sealing 10 to 15 tons (35 to 53 kW) of cooling equipment per day at a single site with one crew.

Large Commercial Sealing

The aerosol-based sealing technology also has been used on a production basis in a large commercial building. The technology was used to seal all of the ductwork in a (~40-year-old) 78,000 ft2 (7200 m2) four-story commercial office building in which duct leakage for the constant volume systems had been identified by test and balance reports.

The sealing for each section in this building, as for all other aerosol sealing applications, is displayed during the sealing process and recorded for future reference by the computer control systems used for all applications. All of the duct sealing added up to 25 separate injections and sealing plots for this building. These results suggest that the 0.1 in. w.g. (25 Pa) reference pressure for fan pressurization is on the high side for this building, as the leakages based upon measurements at this pressure are all higher than the leakages calculated from diffuser measurements in the test and balance reports. On the other hand, the author was unable to determine why the 0.1 in. w.g. (25 Pa) reference pressure seems more appropriate for SF-1 as compared to SF-2 and SF-3, and does not have detailed information on the accuracy of the test and balance reports. Overall, the leakage of the horizontal duct sections was reduced to 2% to 3% of fan flow, and the overall leakage was reduced to less than 5% of fan flow, even including the unsealed duct sections.

Summary and Conclusions

Ducts in commercial buildings leak, particularly in light commercial buildings, which appear to leak more than residential ducts, at least in California. In large commercial buildings some duct systems leak, while others do not, making detection of duct leakage a key activity.

Duct leaks are worth sealing in light commercial buildings whenever the ducts are located above an insulated ceiling. The situation is more complicated in large commercial buildings. Examining large commercial duct leakage from an energy perspective leads to the following considerations: higher leakage, higher exhaust air fractions and ceiling plenum returns make sealing more attractive, whereas induction terminal boxes and ducted returns make sealing less attractive. This article demonstrates that aerosol sealant injection can seal ductwork leaks successfully in light commercial and large commercial existing building applications.

Source: Mark Modera, Ph.D., P.E., Member ASHRAE

AEROSEAL HELPS CONVENTION HOTEL SAVE THOUSANDS

aeroseal_logo_500


CASE STUDY

AEROSEAL HELPS CONVENTION HOTEL SAVE THOUSANDS EACH YEAR IN HEATING & MAINTENANCE COSTS

Capital Plaza Finds Aeroseal Duct Sealing Reduces Monthly Energy Bill, Ends Chronic Mold Problems & Eliminates Cold Spots – Pays for Itself in 18 Months

To say that the owners of the Capital Plaza Hotel in Kentucky were energy conservation skeptics would be an understatement. “If it worked, everyone would be doing it” was a familiar sentiment. Today, however, they are true believers. With the help of Aeroseal, the 10-story hotel and convention center, in the heart of the state’s capitol, has just been Energy Star certified. Owners estimate that duct sealing and other “low hanging” energy saving measures have reduced operating costs by $110,000 a year. Sealing leaks also fixed bathroom exhaust issues, eliminating chronic mold and mildew problems. Cold spots have been replaced with even temperatures throughout the facilities.

In Brief

Building: Capital Plaza Hotel, Frankfort,
Kentuckypic
Aeroseal Contractors: Service Tech, Vandalia, OH
Energy Consultants: Interdependent Energies
Building Specs: 10-story; 160,000 ft2; hotel/convention center. First opened in 1960.
Goal: Reduce duct leaks; save energy; improve IAQ.
Before Aeroseal: Total system leakage: 6,270 CFM*
After Aeroseal: Total system leakage: 771 CFM
Results: a nearly 90% reduction in leakage.
*Cubic feet per minute

The work began with a “proof of concept” demo for the hotel where one section of the building’s entire ductwork system was sealed. The success of that demo led to the bigger project of sealing the hotel’s entire system. The sealing process took five days to complete. Payback is estimated in less than two years. Ongoing savings estimated for duct sealing alone is approximately $24,000/year. Additional savings are expected through reduced maintenance costs and equipment repair. The once skeptical owners are now enthusiastic supporters of aerosol duct sealing and other energy conservation measures for significantly reducing overall operational costs.

Quotes

“During the demo we got to see how the Aeroseal technology actually worked. The computer-generated graph follows the sealing process in real time, and we watched as the leaks were sealed and the CFM of lost air went down to practically nothing. There was no other way, short of tearing down and rebuilding the hotel that we could have gotten anything near these results.”

Chad Braden, Director of Facilities, Capital Plaza

“I was getting quotes for an overhaul of the HVAC system that ran $1 million to $2 million dollars – it would have taken decades to pay back. We opted instead to seal the ductwork with Aeroseal. That dramatically improved the efficiency of the current system, allowed us to reduce energy use related to heating and the use of exhaust fans and it solved a lot of issues related to poor ventilation. We expect pay back on the duct sealing to take less than two years. Then it’s simply ongoing savings right off the top of the hotel’s monthly operating expenses.”

Jason Delambre, Energy Consultant, Interdependent Energies LLC

Aeroseal – The Technology

– Developed at Lawrence Berkeley National Laboratory in 1994.
– Research for Aeroseal was partially funded by the EPA and the U.S. Department of Energy.
– Aeroseal is the only duct sealant technology that is applied from the inside of the duct system. It is delivered as a non-toxic aerosol mist that seeks out and plugs leaks.
– Aeroseal has proven to be 95% effective at sealing air duct leaks.

Aeroseal – The Company

– Aeroseal LLC is a subsidiary of JMD Corporation. The company is dedicated solely to the support of its dealers and the expansion of Aeroseal technology as a primary means of residential and commercial energy conservation.
– Aeroseal is the sole owner and licensee of Aeroseal technology.

For more information about Aeroseal, contact
Aspen Air Duct Cleaning at 
800-931-6653 or email at info@aspenenvironmentalservices.com

Do My Ducts Leak?

Do my ducts leak excessively? Most likely. ASHRAE says that 75% of all ducts in
commercial buildings leak 10-25%. (That’s 200-700% higher than ASHRAE’s recommended standard of 3%!)
To assess your situation, check those which apply:
Evaluate ductwork construction:
___ Do they use slip-and-drive connections on metal ducts?
___ Do they use sheet rock, masonry for air distribution or ventilation shafts?
___ Are there faulty or missing gaskets (can you feel air leaking)?
___ Are there visible holes or gaps at corners, seams, connections or hangers?
___ Is there pressurized external insulation – aka “the air mattress effect”?
Look at the rooms at the end of the hall (ie, far away from fan):
 ___ Is there poor air flow in these rooms?
___ Are these rooms too cold in the winter or too hot in the summer?
Look for uneven air distribution / pressurization issues within the building:
___ Do some areas have excess air flow, while others areas are insufficient?
___ Does airflow delivered vary upon time of year (summer vs. winter)?
___ Are there issues with doors being difficult to open or close?
___ Does the bathroom exhaust grille fail the “two-ply toilet-paper test”?
Ask about occupant complaints:
___ Are there heating or cooling complaints?
___ Are there complaints about moisture, mold, odor, or air quality?
If practical, ask about the fans (the #1 sign of excess energy consumption):
___ Are they unable to setback the air handler at night or weekends?
___ Do fans commonly operate at excessive speeds – ie wide-open?
___ Have motors, pulleys, or sheaves been replaced to provide more airflow?

If you check two or more there is a 90% chance your ducts leak excessively, and cost you money. The US Department of Energy says that sealing ducts is the most cost effective way to reduce HVAC costs. You can save money, with a good payback, while addressing other issues at the same time.